//Caption: Find how they will share 750KVA load at 0.8 power factor lagging //Exa:2.9 clc; clear; close; P_s1=500000//Supplied power(in VA) to first transformer r_1=0.01//Per unit resistance of first transformer x_1=0.05//Per unit reactance of first transformer P_s2=250000//Supplied power(in VA) to second transformer r_2=0.015//Per unit resistance of second transformer x_2=0.04//Per unit reactance of second transformer P_l=750000//Load(in VA) pf=0.8//Powerfactor lagging V_2=400//Secondary voltage of each transformer(in volts) Z_1=r_1+(%i*x_1) Z_2=((2*r_2)+(2*%i*x_2)) Z=Z_1+Z_2 S=P_l*(pf-(%i*(sind(acosd(pf))))) S_1=(S*Z_2)/(Z) s_1=sqrt(((real(S_1))^2)+((imag(S_1)^2))) disp(s_1,'Load on first transformer(in VA)=') S_2=(S*Z_1)/(Z) s_2=sqrt(((real(S_2))^2)+((imag(S_2)^2))) disp(s_2,'Load on second transformer(inVA)=')