//Chapter 10 //Example 10.4 //page no 392 //To draw the zero sequence networks of the system given in example 10.2 clear;clc; //selecting generator rating as base in generator circuit mvab=25; kvGb=11; //base voltage for generator kvTLb=kvGb*(121/10.8); //base voltage for TL kvMb=kvTLb*(10.8/121); //base voltage for motors //Calculation of zero sequence reactance xT0=0.0805; //zero sequence reactance of transformer xG0=0.06; //zero sequence reactance of generator //zero sequence reactanc eof motors xM1_0=0.06*(mvab/15)*(10/kvMb)^2; xM2_0=0.06*(mvab/7.5)*(10/kvMb)^2; x_clr_0=3*2.5*(mvab/kvGb^2); // Reactance of current limiting reactors to be icluded in the zero sequence network x_TL_0=300*(mvab/kvTLb^2); //Zero sequence reactance of TL printf('\n\nTransformer zero sequence reactance = %0.4f pu',xT0); printf('\nGenerator zero sequence reactances = %0.2f pu',xG0); printf('\nZero sequence reactance of motor 1 = %0.3f pu',xM1_0); printf('\nZero sequence reactance of motor 2 = %0.3f pu',xM2_0); printf('\nReactance of current limiting reactors = %0.3f pu',x_clr_0); printf('\nZero sequence reactance of transmission line = %0.3f pu\n\n',x_TL_0); disp('Zero sequence diagram has been drawn using XCOS,simulation has not been done as it is not being asked in the problem');