//Caption:In a single phase transformer Calculate the iron losses and the full load copper losses. //Exam:3.32 clc; clear; close; KVA=400;//Rating of the transformer(in KVA) E_f1=0.9877;//Transformer efficiency when delivering full load at 0.8 power factor P_f1=0.8;//power factor at full load P_f2=1;//power factor at half load O_p1=KVA*P_f1;//Output on full load when power factor is 0.8(in KW) I_p1=(O_p1/E_f1);//Input on full load when power factor is 0.8(in KW) P_t1=I_p1-O_p1;//Total losses on full load when power factor is 0.8(in KW) O_p2=(1/2)*KVA*P_f2;//Output at half load when power factor is 1 E_f2=0.9913;//Transformer efficiency when delivering half load at 1 power factor I_p2=O_p2/E_f2;//Input at half load when power factor is 1 P_t2=I_p2-O_p2//Total losses at half load when power factor is 1 //P_t1=P_c+P_i //P_t2=(1/4)P_c+P_i P_c=(4/3)*(P_t1-P_t2);//Full load and copper losses P_i=(1/3)*(4*P_t2-P_t1);//iron losses disp(P_c,'full load and copper losses(in KW)='); disp(P_i,'iron loss(in KW)=');