clc(); clear; // To calculate the outside tube area for a single-pass steam condenser Do=1/12; // Outside diameter of the condenser in ft Di=0.902/12; // Outside diameter of the condenser in ft Ts=81.7; // Steam temperature in degF Tw1=61.4; // Water inlet temperature in degF Tw2=69.9; // Water outlet temperature in degF k=63; // Thermal conductivity in Btu/hr-ft-degF v=7; // average velocity in ft/sec h1=1270; // water side film coefficient i Btu/hr-ft^2-degF h2=1000; // Steam side film coefficient in Btu/hr-ft^2-degF U=1/((Do/(Di*h1))+(Do*log(Do/Di)/(2*k))+(1/h2)); // Heat transfer coefficient LMTD=((Ts-Tw1)-(Ts-Tw2))/log((Ts-Tw1)/(Ts-Tw2)); // Log mean temperature diff. m=731300; // Saturated steam to be handled in lb/hr L=1097.4-49.7; // Change in enthalpy in Btu/lb q=m*L; // Heat required in Btu/hr A=q/(U*LMTD); // Area of condenser in ft^2 printf("The area of steam condenser is %d ft^2",A);