clc //For air at 35 0C DBT and 50% RH p_vs=0.0563; //bar; At 35 0C, from steam tables phi=0.5; p_t=1.0132; t_db1=35; //0C t_dp1=23; //0C cp=1.005; R=287; p_v=phi*p_vs; W1=0.622*p_v/(p_t-p_v); h_g1=2565.3; //kJ/kg h_vapour=h_g1 + 1.88*(t_db1 - t_dp1); h1=cp*t_db1+W1*h_vapour; disp("(i) R.H. of cooled air") p_vs=0.0317; phi=p_v/p_vs; disp("RH of cooled air=") disp(phi*100) disp("%") disp("(ii) Heat removed from air") h_g2=2547.2; //kJ/kg t_db2=25; //0C t_dp2=23; //0C W2=W1; T=308; //K V=40; //m^3 h_vapour=h_g2 + 1.88*(t_db2 - t_dp2); h2=cp*t_db2+W2*h_vapour; m=(p_t-p_v)*10^5*V/R/T; //Let Heat removed be denoted by H H=m*(h1-h2); disp("Heat removed =") disp(H) disp("kJ")