clc disp("(i) Mass of spray water required") //At 22 0c p_vs=0.0264; //bar phi_3=0.55; p_t=1.0132; //bar p_v3=phi_3*p_vs; W3=0.622*p_v3/(p_t-p_v3); //At 3 0C p_vs1=0.0076; //bar p_v1=p_vs1; W1=0.622*p_v1/(p_t-p_v1); R=287; T_3=295; //K v=R*T_3/(p_t-p_v3)/10^5; m=(W3-W1)/v; disp(" Mass of spray water required=") disp(m) disp("kg moisture/m^3") disp("(ii) Temperature to which the air must be heated") t_dp=12.5; //0C cp=1.005; t_db3=22; //0C h_g3=2524; //kJ/kg h_vapour3=h_g3 + 1.88*(t_db3 - t_dp); W2=0.0047; h_g2=2524; //kJ/kg h4=41.87; t_db2=(cp*t_db3 + W3*h_vapour3 -W2*h_g2 + 1.88*W2*t_dp - (W3-W2)*h4)/(cp-W2*1.88); disp("t_db2=") disp(t_db2) disp("0C")