//Electric Power Generation, Transmission and Distribution by S.N.Singh //Publisher:PHI Learning Private Limited //Year: 2012 ; Edition - 2 //Example 14.1 //Scilab Version : 6.0.0 ; OS : Windows clc; clear; d=600; //Distance between three conductors in cm b=72; //Pressure in Hg r=1; //Radius of the conductor in cm t=27; //Air temperature in Celcius m=0.90; //Irregularity factor mv=0.82; //Surface factor adf=3.92*b/(273+t); //Air density factor Vc=r*21.1*m*0.9408*log(d/r); //Phase to neutral critical disruptive voltage in kV cdv=Vc*sqrt(3); //Line to line critical disruptive voltage in kV Vv=21.1*mv*r*0.9408*(1+(0.3/sqrt(r*0.9408)))*log(d/r); //Critical visual disruptive voltage cvdv=Vv*sqrt(3); //Line to line critical visual disruptive voltage in kV printf("\nThe critical disruptive voltage is %.2f kV",cdv); printf("\nThe visual critical disruptive voltage is %.2f kV",cvdv);