//Electric Power Generation, Transmission and Distribution by S.N.Singh //Publisher:PHI Learning Private Limited //Year: 2012 ; Edition - 2 //Example 10.10 //Scilab Version : 6.0.0 ; OS : Windows clc; clear; r=0.05; //Radius of the conductor in m bc=5; //Distance between b & c in m bb1=3*bc; //Distance between b & b1 in m aa1=2*bc; //Distance between a & a1 in in m ab=(((bb1-aa1)/2)^(2)+bc^(2))^(1/2); ab1=((aa1+((bb1-aa1)/2))^(2)+bc^(2))^(1/2); ac1=((bc*2-((bb1-aa1)/2))^(2)+bc^(2))^(1/2); Dab=nthroot(ab*ab1*ab1*ab,4); Dbc=nthroot(bc*aa1*aa1*bc,4); Dca=nthroot(ab*ac1*ab*ac1,4); Deq=nthroot(Dab*Dbc*Dca,3); Dsa=sqrt(aa1*0.7788*r); Dsb=sqrt(bb1*0.7788*r); Dsc=sqrt(bc*0.7788*r); Ds=nthroot(Dsa*Dsb*Dsc,3); L=(2*10^(-7)*log(Deq/Ds))*10^(6); //Inductance of double circuit in mH/km/phase Dsa1=sqrt(aa1*r); //GMR for capacitance Dsb1=sqrt(bb1*r); //GMR for capacitance Dsc1=sqrt(bc*r); //GMR for capacitance Ds1=nthroot(Dsa1*Dsb1*Dsc1,3); //Equivalent GMR for capacitance C=(2*%pi*(10^(-9)/(36*%pi)))/log(Deq/Ds1); //Capacitance of double circuit in nF/km/phase printf("\nInductance of the line is %.3f mH/km/phase",L); printf("\nCapacitance of the line is %.2f nF/km/phase",C/10^(-12)); //Variation present in result due to wrong calculation of Ds1 value