clear // // Variable declaration // From example 25.2 Q=16.4// Total load in kW T_in=33// The temperature at liquid R134a enters the expansion valve in °C T_out=9// The temperature at liquid R134a leaves the cooler in °C T_e=5// The temperature at which liquid R134a evaporates in °C // Calculation h_v=405.23// Enthalpy of R134a,superheated to 9 C in kJ/kg h_f=246.71// Enthalpy of liquid R134a at 33 C in kJ/kg Re=h_v-h_f// Refrigerating effect in kJ/kg m_r=Q/Re// Required refrigerant mass flow in kg/s printf("\n Required refrigerant mass flow=%0.3f kg/s",m_r)