clear // Variable declaration T_d=23// The dry bulb temperature in °C H=40// % saturation SH=36// The sensible heat to be removed in kW LH=14// The latent heat in kW // Calculation // Plotting on the chart ( Figure 21.10 ) from 23°C/40% and using the ratio R=SH/(SH+LH) printf("\n The process line meets the saturation curve at - 1°C, giving the ADP (which meansthat condensate will collect on the fins as frost).") printf("\n Taking the condition at 5°C dry bulb and measuring the proportion along theprocess line gives a coil contact factor of 75")