//Book - Power system: Analysisi & Design 5th Edition //Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J.Overbye //Chapter-9 ;Example 9.2 //Scilab Version - 6.0.0; OS - Windows clc; clear; Xn=0.05 //motor neutral is grounded through reactance in per unit Sb=100 //Base value of system in MVA Vb=13.8 //Base voltage of system in kV Vf=1.05 //Prefault voltage in per unit Z1=%i*0.13893 //Positive sequence impedance in per unit If=Vf/Z1 //positive sequence fault current in per unit a=exp(%i*(120)*(%pi/180)) //operator a Isf=[1 1 1;1 (a^2) a;1 a (a^2)]*[0;If;0] //subtransient fault current in each phase in per unit disp(abs(Isf),'The magnitude of fault current in each phase in per unit is given by :',); disp(atand(imag(Isf),real(Isf)),'The angle of fault current in each phase in degrees is given by:',);