//Book - Power System: Analysis & Design 5th Edition //Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye //Chapter - 8 ; Example 8.5 //Scilab Version - 6.0.0 ; OS - Windows clc; clear; Zn = %i*10; //generator neutral impedance in ohm Zgo = %i*1; //generator zero sequence impedance in ohm Zg1 = %i*15; //generator positive sequence impedance in ohm Zg2 = %i*3; //generator negative sequence impedance in ohm Zl1 = 0.087+(%i*0.99); //line impedace in ohm Zdel = 22.98+%i*(19.281); //impedance of the delta load in ohm V1=(415.69-(%i*240))/sqrt(3); //RMS line to neutral phase voltage of AC supply in Volts I1 = V1/(Zl1+((1/3)*Zdel)); //sequence component of line current in A printf('\nThe sequence component of the line current Ia is %.4f amperes and its angle is %.4f degree ',abs(I1), atand(imag(I1), real(I1)));