// Book - Power System: Analysis & Design 5th Edition // Authors - J. Duncan Glover, Mulukutla S. Sharma, Thomas J. Overbye // Chapter - 5 : Example 5.7 // Scilab Version 6.0.0 : OS - Windows clc; clear; p = 9000; // Power in MW l = 500; // Load center distance from the plant in km f = 60; // Frequency in Hz Vs = 1.0; // Sending end voltage in per unit Vr = 0.95; // Receiving end voltage in per unit delta = 35*(%pi/180); // Phase angle in degree lamdba = 5000; // Wavelength in km v1 = 345; // 1st line voltage in kV Zc1 = 297; // Characteristic impedance of 1st line in Ohm SIL1 = (v1^2)/Zc1; // Surge Impedance Load for line 1 in MW P1 = (Vs*Vr*SIL1*sin(delta))/(sin((2*%pi*l)/lamdba)); // Real power delivered for line 1 without losses in MW/line line1 = ceil((p/P1)+1); // Lines required to transmit 9000 MW power with 345 kV line out of service v2 = 500; // 2nd line voltage in kV Zc2 = 277; // Characteristic impedance of 2nd line in Ohm SIL2 = (v2^2)/Zc2; // Surge Impedance Load for line 2 in MW P2 = (Vs*Vr*SIL2*sin(delta))/(sin((2*%pi*l)/lamdba)); // Real power delivered for line 2 without losses in MW/line line2 = ceil((p/P2)+1); // Lines required to transmit 9000 MW power with 500 kV line out of service v3 = 765; // 3rd line voltage in kV Zc3 = 266; // Characteristic impedance of 3rd line in Ohm SIL3 = (v3^2)/Zc3; // Surge Impedance Load for line 3 in MW P3 = (Vs*Vr*SIL3*sin(delta))/(sin((2*%pi*l)/lamdba)); // Real power delivered for line 3 without losses in MW/line line3 = ceil((p/P3)+1); // Lines required to transmit 9000 MW power with 765 kV line out of service printf('\n Surge Impedance Load for line 1 is = %0.0f MW', SIL1); printf('\nReal power delivered for line 1 without losses is = %0.0f MW/line', P1); printf('\nLines required to transmit 9000 MW power with 345 kV line out of service is = %0.0f', line1); printf('\n\nSurge Impedance Load for line 2 is = %0.0f MW', SIL2); printf('\nReal power delivered for line 2 without losses is = %0.0f MW/line', P2); printf('\nLines required to transmit 9000 MW power with 500 kV line out of service is = %0.0f', line2); printf('\n\n Surge Impedance Load for line 3 is = %0.0f MW', SIL3); printf('\nReal power delivered for line 3 without losses is = %0.0f MW/line', P3); printf('\nLines required to transmit 9000 MW power with 765 kV line out of service is = %0.0f', line3);