//Book - Power system: Analysisi & Design 5th Edition //Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J.Overbye //Chapter-3 ;Example 3.9 //Scilab Version - 6.0.0; OS - Windows clc; clear; Sb=300 //rated power of transformer in MVA Vb1=13.8 // Terminal 1 base voltage in kV Vb2=199.2 // Terminal 2 base voltage in kV Vb3=19.92 // Terminal 3 base voltage in kV X12old=0.10 //given per unit leakage reactance terminal 1 and 2 X13old=0.16 //given per unit leakage reactance terminal 1 and 3 X23old=0.14 //given per unit leakage reactance terminal 2 and 3 Sb12=300 //rated power corresponding to leakage reactance X12 in MVA Sb13=50 //rated power corresponding to leakage reactance X13 in MVA Sb23=50 //rated power corresponding to leakage reactance X23 in MVA X12new=X12old*(Sb/Sb12) //new per unit leakage reactance terminal 1 and 2 X13new=X13old*(Sb/Sb13) //new per unit leakage reactance terminal 1 and 3 X23new=X23old*(Sb/Sb23) //new per unit leakage reactance terminal 2 and 3 X1=(1/2)*(X12new+X13new-X23new) X2=(1/2)*(X12new+X23new-X13new) X3=(1/2)*(X13new+X23new-X12new) printf('The new per unit leakage reactance terminal 1 and 2 is %.4f pu\n',X12new); printf('The new per unit leakage reactance terminal 1 and 3 is %.4f pu\n',X13new); printf('The new per unit leakage reactance terminal 2 and 3 is %.4f pu\n',X23new); printf('The per unit reactance of terminal 1 is %.4f pu\n',X1); printf('The per unit reactance of terminal 2 is %.4f pu\n',X2); printf('The per unit reactance of terminal 3 is %.4f pu\n',X3);