//Book - Power System: Analysis & Design 5th Edition //Authors - J. Duncan Glover, Mulukutla S. Sarma, and Thomas J. Overbye //Chapter - 12 ; Example 12.3 //Scilab Version - 6.0.0 ; OS - Windows clc; clear; M=500; //MVA rating of the generator f=60; //requency in Hertz R=0.05; //Regulation constant in pu delF=0.01; //Increase in frequency in Hertz delFpu=delF/f; //Frequency increase in pu delPref=0; //Since fixed reference power setting is assumed delPmpu=delPref-(1/R)*delFpu //Change in mechanical power in pu delPm=delPmpu*M; //Actual value of mechanical power in MW printf('The turbine mechanical power output decreases by %.3f MW.',abs(delPm))