//Chapter 6:Induction Motor Drives //Example 13 clc; //Variable Initialization //Ratings of the star connected Induction motor are same as that of Ex-6.9 f=50 // frequency in HZ Vl=400 //line voltage in V P=4 // number of poles N=1370 //rated speed //Parameters referred to the stator Xr_=3.5 // rotor winding reactance in ohm Xs=Xr_ // stator winding reactance in ohm Rr_=3 // resistance of the rotor windings in ohm Rs=2 // resistance of the stator windings in ohm //Solution Wms=4*%pi*f/P f1=60 //frequency in Hz during speed control of the motor K=f1/f //the value of K at 60Hz x=Rs+sqrt(Rs**2+K**2*(Xs+Xr_)**2) Tmax_=3/(2*K*Wms)*(Vl/sqrt(3))**2/x //torque at 60 Hz frequency z=Rs+sqrt(Rs**2+(Xs+Xr_)**2) Tmax=3/(2*Wms)*(Vl/sqrt(3))**2/z //maximum torque ratio=Tmax_/Tmax //ratio //Result mprintf("Ratio of Motor breakdown torque at 60Hz to rated torque at 50Hz is:%.3f",ratio)