clc // Given that DBT = 31 // Dry bulb temperature in degree celsius WBT = 18.5 // Wet bulb temperature in degree celsius t = 4.4 // Effective surface temperature of coil in degree celsius RE = 12.5 // Refrigeration effect by the coil in kW f= 39.6 // Air flow rate in cmm printf("\n Example 15.11 \n") // From the fig. given in the example ws = 5.25 //In g/kg d.a. hs = 17.7 //In kJ/kg d.a. v1 = 0.872 // In m^3/kg d.a. h1 = 52.5 // In kJ/kg d.a. w1 = 8.2 // In g/kg d.a. G = f/v1 h2 = h1-(RE*60)/G w2 = w1-((h1-h2)/(h1-hs))*(w1-ws) // From the psychrometric chart t2 = 18.6 // In degree celsius t_ = 12.5 // In degree celsius x = (h2-hs)/(h1-hs) printf("\n DBT of air leaving the coil is %f degree celsius,\n WBT of air leaving the coil is %f degree celsius,\n Coil bypass factor is %f ",t2,t_,x) // Answer varies due to round off error