// Calculating the maximum flux and no load current of the transformer clc; disp('Example 5.18, Page No. = 5.99') // Given Data Ep = 400;// Primary winding voltage (in volts) f = 50;// Frequency (in Hz) A = 2.5*10^(-3);// Area of cross section (in meter square) Sf = 0.9;// Stacking factor Tp = 800;// Primary winding turns li = 2.5;// Length of the flux path (in meter) u0 = 4*%pi*10^(-7);// Permeability of free space ur = 1000;// Relative ermeability D = 7.8*10^(3);// Density of iron (in kg per meter cube) FD_w = 2.6;// Working flux density (in W per kg) // Calculation of the maximum flux Ai = Sf*A;// Net iron area (in meter square) Bm = Ep/(4.44*f*Ai*Tp);// Maximum flux density of core (in Wb per meter square) Fm = Bm*Ai;// Maximum flux in the core (in Wb) disp(Fm,'Maximum flux in the core (Wb)='); // Calculation of the no load current AT0 = li/(ur*u0)*Bm;// Magnetic mmf (in A) Im = AT0/(2^(1/2)*Tp);// Magnetising current (in A) V = Ai*li;// Volume of the core (in meter cube) W = V*D;// Weight of core (in kg) Pi = W*FD_w;// Iron loss (in W) Il = Pi/Ep;// Loss component of no load current (in A) I0 =(Im*Im+Il*Il)^(1/2);// No load current (in A) disp(I0,'No load current (Ampere)='); //in book answers are 0.00225 (Wb) and 1.77 (Ampere) respectively. The answers vary due to round off error