// Calculating the per unit leakage reactance clc; disp('Example 5.14, Page No. = 5.90') // Given Data // 2000/400 V, single phase shell type transformer Q = 100;// kVA rating f = 50;// Frequency (in Hz) u0 = 4*%pi*10^(-7); Tp = 200;// h.v winding turns Lmt = 1.5;// Length of mean turn (in meter) W = 0.12;// Width of winding (in meter) a = 0.016;// Width of duct between h.v and l.v. windings (in meter) bp = 0.04;// Width of h.v. winding (in meter) bs = 0.036;// Width of l.v. winding (in meter) // Calculation of the per unit leakage reactance Xp = %pi*f*u0*Tp*Tp/2*Lmt/W*(a+(bp+bs)/6);// Leakage reactance referred to the primary side (ohm) I_hv = Q*10^(3)/2000;// H.V. winding current at full load (in ampere) Xp_pu = Xp*I_hv/2000;// Per unit leakage reactance disp(Xp_pu,'Per unit leakage reactance='); //in book answer is 0.0353. The answers vary due to round off error