// Calculating the efficiency of machine and amount of cooling water clc; disp('Example 4.23, Page No. = 4.50') // Given Data MVA = 30;// MVA rating of turbo-alternator Ti = 15;// Inlet temperature of air (in degree celsius) To = 45;// Outlet temperature of air (in degree celsius) H = 750;// Baromatric height (in mm of mercury) Va = 30;// Volume of air (in meter cube per second) nf = 0.4;// Fan efficiency cp = 1000;// Specific heat of air at constant pressure (in J per kg per degree celsius) V = 0.78;// Volume of 1 kg of air at N.T.P. (in meter cube) pf = 0.8;// Power factor // Calculation of the efficiency of machine T = To-Ti;// Temperature rise limit (in degree celsius) Q = Va/((V*10^(3)/(cp*T))*((Ti+273)/273)*(760/H));// Total losses (in kW) P_out = 30*10^(3)*pf;// Output power (in kW) n = P_out/(P_out+Q)*100;// Fan power (in kW) disp(n,'(a) Efficiency of machine (in percentage)='); // Calculation of the amount of cooling water T = 8;// Temperature rise of water (in degree celsius) Vw = 0.24*Q/T;// Amount of cooling water (in litre per second) disp(Vw,'(b) Amount of cooling water (litre per second)='); //in book efficiency is equal to 95.7% and amount of cooling water 32.4 (litre per second). The answers vary due to round off error