// Example 9.7 // Determine (a) Active and reactive components of the bus load (b) If the // power factor of generator A is 0.94 lagging, determine the reactive power // supplied by each machine. // Page 366 clc; clear; close; // Given data Pbuspower=500; // Power supplied Pind=200; // Induction motor power PF=0.852; // Percent power factor NA=2; // Number of alternators LPF=0.94; // Lagging power factor // (a) Active and reactive components of the bus load Pbus=Pbuspower+Pind*PF; // Active component of the bus load ThetaMot=acosd(PF); // Power angle of motor Qbus=Pind*sind(ThetaMot); // Reactive component the bus load // (b) Reactive power supplied by each machine Pa=Pbus/NA; // Alternator A power ThetaA=acosd(LPF); // Alternator A angle Qa=tand(ThetaA)*Pa; // Reactive power supplied by machine A Qb=Qbus-Qa; // Reactive power supplied by machine B // Display result on command window printf("\n Active component of the bus load = %0.2f kW ",Pbus); printf("\n Reactive component of the bus load = %0.1f kvar",Qbus); printf("\n Reactive power supplied by machine A = %0.1f kvar",Qa); printf("\n Reactive power supplied by machine B = %0.1f kvar",Qb);