// Example 5.21 // Computation of Inductance and voltage rating of each series connected // inductor required to limit the starting current to approximately 2*Irated. // Page No. 236 clc; clear all; close; // Given data KVA=6.7; // Average locked rotor KVA/hp hp=7.5; // Motor horsepower Vline=208; // Line voltage I=48; // Total current Rlr=0.294; // Locked rotor resistance Xlr=0.809; // Locked rotor impedance f=60; // Frequency of motor // Corresponding approximate load current Ilr=KVA*1000*hp/(sqrt(3)*Vline); Vphase=Vline/sqrt(3); // Voltage/phase // Applying ohm's law to one phase Zlr=Vphase/Ilr; // Impedance Xex=sqrt((Vphase^2/I^2)-(Rlr^2))-Xlr; L=Xex/(2*%pi*f); L=L*10^03; VXl=I*Xex; // Display result on command window printf("\n The inductance of each series connected inductor = %0.2f mH ",L); printf("\n The voltage rating of each series connected inductor = %0.1f V ",VXl);