// Example 3.7 // Computation of (a) Bank ratio (b) Transformer ratio (c) Rated line and phase // currents for the high side (d) Rated line and phase currents for the low side // Page No. 113 clc; clear; close; // Given data VLINEHS=4160; // Number of turns in the high side VLINELS=240; // Number of turns in the low side VHS=2400; // Voltage at the high side S=4800; // Supply voltage Vline=150000; // Transformer rating // (a) Bank ratio bankratio=VLINEHS/VLINELS; // (b) Transformer ratio Vphasep= VLINEHS/ sqrt(3); // For wye primary Vphases=VLINELS // For secondary TR=Vphasep/Vphases; // Transformer ratio //(c) Rated line and phase currents for the high side Ilinew=Vline/(sqrt(3)*VLINEHS); Iphasew=Ilinew; // (d) Rated line and phase currents for the low side Ilined=Vline/(sqrt(3)*VLINELS); Iphased=Ilined/sqrt(3); // Display result on command window printf("\n Bank ratio = %0.1f ",bankratio); printf("\n Transformer ratio = %0.1f ",TR); printf("\n Rated line current for the high side = %0.1f A ",Ilinew); printf("\n Rated phase current for the high side = %0.1f A ",Iphasew); printf("\n Rated line current for the low side = %0.1f A ",Ilined); printf("\n Rated phase current for the low side = %0.1f A ",Iphased);