// Example 2.11 // Computation of transformer regulation // Page No. 71 clc; clear; close; // Given data S=10; // Transformer actual rating 10KVA Srated=25; // Rated 25KVA PF=0.65; // Power factor lagging RPU=0.0124; // Percent resistance drop XPU=0.014; // Percent reactance drop // Transformer regulation SPU=S/Srated; SPU=SPU*100; Theta=acosd(PF); // Transformer regulation RegPU=sqrt( ( (RPU*SPU+PF)^2)+ ((XPU*SPU+sind(Theta))^2))-1; // Transformer regulation in percentage RegPU_Per=RegPU*100; // Display result on command window printf("\n Transformer regulation = %0.3f ",RegPU); printf("\n Transformer regulation in percentage= %0.1f ",RegPU_Per); // Answer varies due to round off errors