// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART III : SWITCHGEAR AND PROTECTION // CHAPTER 8: PROTECTION OF ALTERNATORS AND AC MOTORS // EXAMPLE : 8.4 : // Page number 625 clear ; clc ; close ; // Clear the work space and console // Given data I_min = 0.15 // Minimum pick up current of relay(A) slope = 12.0 // Slope(%) CT_ratio = 400.0/5 // CT ratio I_1 = 360.0 // Current(A) I_2 = 300.0 // Current(A) // Calculations i_1 = I_1/CT_ratio // Current(A) i_2 = I_2/CT_ratio // Current(A) percentage = (i_1-i_2)/((i_1+i_2)/2)*100 // Percentage(%) // Results disp("PART III - EXAMPLE : 8.4 : SOLUTION :-") if(percentage>slope) then printf("\nRelay would trip the circuit breaker, since the point lie on +ve torque regime") else then printf("\nRelay would not trip the circuit breaker, since the point do not lie on +ve torque regime") end