// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART III : SWITCHGEAR AND PROTECTION // CHAPTER 7: PROTECTIVE RELAYS // EXAMPLE : 7.3 : // Page number 596 clear ; clc ; close ; // Clear the work space and console // Given data MVA = 20.0 // Transformer MVA overload = 30.0 // Overload of transformer(%) kV = 11.0 // Bus bar rating(kV) CT_trans = 1000.0/5 // Transformer CT CT_cb = 400.0/5 // Circuit breaker CT ps = 125.0 // Plug setting(%) ts = 0.3 // Time setting I_f = 5000.0 // Fault current(A) t_margin = 0.5 // Discriminative time margin(sec) // Calculations I_sec_fault = I_f/CT_cb // Secondary fault current(A) CT_cb_sec = 5.0 // Secondary turn PSM = I_sec_fault/(ps/100*CT_cb_sec) // Plug setting multiplier t = 2.8 // Time against this PSM(sec). From graph E7.1 in textbook page no 595 time_oper = t*ts // Operating time of feeder relay(sec) I_ol = (1+(overload/100))*MVA*1000/(3**0.5*kV) // Overload current(A) I_sec_T = I_ol/CT_trans // Secondary current(A) CT_T_sec = 5.0 // Secondary turn of transformer PSM_T = I_sec_T/CT_T_sec // Minimum plug setting multiplier of transformer I_sec_T1 = I_f/CT_trans // Secondary fault current(A) ps_T1 = 1.5 // Plug setting as per standard value PSM_T1 = I_sec_T1/(CT_T_sec*ps) // Plug setting multiplier of transformer t_T1 = 7.0 // Time against this PSM(sec). From graph E7.1 in textbook page no 595 time_setting = (time_oper+t_margin)/t_T1 // Time setting of transformer // Results disp("PART III - EXAMPLE : 7.3 : SOLUTION :-") printf("\nOperating time of feeder relay = %.2f sec", time_oper) printf("\nMinimum plug setting of transformer relay, P.S > %.2f ", PSM_T) printf("\nTime setting of transformer = %.3f ", time_setting)