// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART III : SWITCHGEAR AND PROTECTION // CHAPTER 7: PROTECTIVE RELAYS // EXAMPLE : 7.2 : // Page number 596 clear ; clc ; close ; // Clear the work space and console // Given data ratio = 525.0/1 // CT ratio CT_sec = 1.0 // Secondary turn t_mult = 0.3 // Time multiplier setting I_f = 5250.0 // Fault current(A) // Calculations I_sec_fault = I_f/ratio // Secondary fault current(A) PSM = I_sec_fault/(1.25*CT_sec) // Plug setting multiplier t = 3.15 // Time against this PSM(sec). From graph E7.1 in textbook page no 595 time_oper = t*t_mult // Operating time(sec) // Results disp("PART III - EXAMPLE : 7.2 : SOLUTION :-") printf("\nTime of operation of the relay = %.3f sec", time_oper)