// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART III : SWITCHGEAR AND PROTECTION // CHAPTER 4: UNSYMMETRICAL FAULTS IN POWER SYSTEMS // EXAMPLE : 4.9 : // Page number 519 clear ; clc ; close ; // Clear the work space and console // Given data MVA_G = 10.0 // Generator rating(MVA) kV_G = 11.0 // Generator rating(kV) X_1_G = 27.0 // Positive sequence reactance of generator(p.u) X_2_G = 9.0 // Negative sequence reactance of generator(p.u) X_0_G = 4.5 // Zero sequence reactance of generator(p.u) X_1_L = 9.0 // Positive sequence reactance of line upto fault(p.u) X_2_L = 9.0 // Negative sequence reactance of line upto fault(p.u) X_0_L = 0 // Zero sequence reactance of line upto fault(p.u) // Calculations E_a = kV_G*1000/3**0.5 // Phase voltage(V) Z_1 = %i*(X_1_G+X_1_L) // Positive sequence reactance(p.u) Z_2 = %i*(X_2_G+X_2_L) // Negative sequence reactance(p.u) I_b = %i*3**0.5*E_a/(Z_1+Z_2) // Fault current in line b(p.u) I_c = -I_b // Fault current in line c(p.u) // Results disp("PART III - EXAMPLE : 4.9 : SOLUTION :-") printf("\nFault current in line b, I_b = %.f A", abs(I_b)) printf("\nFault current in line c, I_c = %.f A", real(I_c))