// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART II : TRANSMISSION AND DISTRIBUTION // CHAPTER 15: INSULATION CO-ORDINATION // EXAMPLE : 15.1 : // Page number 398-399 clear ; clc ; close ; // Clear the work space and console // Given data L = 30.0 // Height of arrester located(m) BIL = 650.0 // BIL(kV) de_dt = 1000.0 // Rate of rising surge wave front(kV/ยต-sec) V = 132.0 // Transformer voltage at HV side(kV) E_a = 400.0 // Discharge voltage of arrester(kV) v = 3.0*10**8 // Velocity of surge propagation(m/sec) // Calculations E_t = E_a+(2.0*de_dt*L/300) // Highest voltage the transformer is subjected(kV) // Results disp("PART II - EXAMPLE : 15.1 : SOLUTION :-") printf("\nHighest voltage to which the transformer is subjected, E_t = %.f kV", E_t)