// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART II : TRANSMISSION AND DISTRIBUTION // CHAPTER 10: POWER SYSTEM STABILITY // EXAMPLE : 10.28 : // Page number 310 clear ; clc ; close ; // Clear the work space and console // Given data sin_delta_0 = 0.45 // Supplying percent of peak power capacity before fault x = 4.0 // Reactance under fault increased gamma_2 = 0.7 // Peak power delivered after fault clearance // Calculations delta_0 = asin(sin_delta_0) // δ_0(radians) delta_0_degree = delta_0*180/%pi // δ_0(°) gamma_1 = 1.0/x // γ_1 delta_m = %pi-asin(sin_delta_0/(gamma_2)) // δ_m(radians) delta_m_degree = delta_m*180/%pi // δ_m(°) delta_c = acosd(1.0/(gamma_2-gamma_1)*((delta_m-delta_0)*sin(delta_0)+(gamma_2*cos(delta_m)-gamma_1*cos(delta_0)))) // Clearing angle(°) // Results disp("PART II - EXAMPLE : 10.28 : SOLUTION :-") printf("\nCritical clearing angle, δ_c = %.f° ", delta_c)