// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART II : TRANSMISSION AND DISTRIBUTION // CHAPTER 8: CORONA // EXAMPLE : 8.8 : // Page number 230 clear ; clc ; close ; // Clear the work space and console // Given data d = 2.0 // Diameter of conductor(cm) D = 150.0 // Spacing b/w conductor(cm) delta = 1.0 // Air density factor // Calculations r = d/2.0 // Radius of conductor(cm) V_d = 21.1*delta*r*log(D/r) // Disruptive critical voltage(kV/phase) V_d_ll = 3**0.5*V_d // Line voltage for commencing of corona(kV) // Results disp("PART II - EXAMPLE : 8.8 : SOLUTION :-") printf("\nLine voltage for commencing of corona = %.2f kV \n", V_d_ll) printf("\nNOTE: Solution is incomplete in textbook")