// A Texbook on POWER SYSTEM ENGINEERING // A.Chakrabarti, M.L.Soni, P.V.Gupta, U.S.Bhatnagar // DHANPAT RAI & Co. // SECOND EDITION // PART II : TRANSMISSION AND DISTRIBUTION // CHAPTER 8: CORONA // EXAMPLE : 8.6 : // Page number 229 clear ; clc ; close ; // Clear the work space and console // Given data P_c1 = 53.0 // Total corona loss(kW) V_1 = 106.0 // Operating line voltage(kV) P_c2 = 98.0 // Total corona loss(kW) V_2 = 110.9 // Operating line voltage(kV) V_3 = 113.0 // Operating line voltage(kV) // Calculations E_1 = V_1/3**0.5 // Phase voltage(kV) E_2 = V_2/3**0.5 // Phase voltage(kV) P_ratio = (P_c2/P_c1)**0.5 E_0 = (P_ratio*E_1-E_2)/(P_ratio-1) // Disruptive critical voltage(kV) E_3 = V_3/3**0.5 // Phase voltage(kV) W = ((E_3-E_0)/(E_1-E_0))**2*P_c1 // Corona loss at 113 kV(kW) // Results disp("PART II - EXAMPLE : 8.6 : SOLUTION :-") printf("\nDisruptive critical voltage, E_0 = %.f kV", E_0) printf("\nCorona loss at 113 kV, W = %.f kW\n", W) printf("\nNOTE: Changes in obtained answer from textbook is due to more precision here")