// Variable Declaration kv_hv = 66.0 //Voltage rating of HV side of transformer(kV) kv_lv = 11.0 //Voltage rating of LV side of transformer(kV) CT = 300.0/5 //CT ratio on low tension side // Calculation Section I = 300.0 //Assumed current flowing at low tension side(A) I_HT = kv_lv/kv_hv*I //Line current on HT side(A) I_LT_CT = I/CT //Pilot wire current from LT side(A) CT_ratio_HT = I_HT*3**0.5/I_LT_CT //Ratio of CT on HT side // Result Section printf('Ratio of CT on high tension side = %.f√3/%.f' ,I_HT,I_LT_CT)