//Example 5.21 clc;clear;close; format('v',6); C1=300;//MW C2=400;//MW G1=4;//%//droop characteristics of governer G2=6;//%//droop characteristics of governer L=400;//MW f=50;//Hz L1=C1*L/(C1+C2);//MW//Load on 300 MW generator L2=L*C2/(C1+C2);//MW//Load on 400 MW generator f01=f*(C1)/(C1-G1/100*L1);//Hz///No load frequency disp(f01,"No load frequency of 300 MW generator(Hz)"); f02=f*(C2)/(C2-G2/100*L2);//Hz///No load frequency disp(f02,"No load frequency of 400 MW generator(Hz)");