// Example 4.9;parameter of primary side ,regulation and efficiency clc; close; clear; //given format('v',6) po=100;//watts v1=200;//volts io=1;//amperes ocpf=po/(v1*io);//open circuit power factor sinpf=sqrt(1-ocpf^2);// im=io*sinpf;//in amperes iw=io*ocpf;//current in amperes rm=v1/iw;//ohms xm=v1/im;//in ohms vs=15;//volts ia=10;//amperes zo2=vs/ia;//in ohms wa=85;//watts ro2=wa/(ia)^2;//ohms e2=400;//volts e1=200;//volts k=e2/e1;//transformation ratio zo1=zo2/k^2;//ohms ro1=ro2/k^2;//ohms xo1=sqrt(zo1^2-ro1^2);//ohms disp(" part (a)") disp(im,"magnetising component of no load current (Im) is,(A)=") disp(iw,"working component of no load current (Iw) is,(A)=") disp(rm,"resistance for primary side (Rm) is,(Ohm)=") disp(xm,"reactance for primary ohms (Xm) is,(Ohm)=") disp(xo1,"impedence for primary side (X01) is,(Ohm)=") disp("part (b)") kva=4000;//kVA i2=kva/e2;//in amperes xo2=sqrt(zo2^2-ro2^2);//ohms pf=0.8;// power factor vlag=i2*(ro2*pf+xo2*sqrt(1-pf^2));//in volts prld=(vlag*po)/e2;// vlag1=i2*(ro2*pf-xo2*sqrt(1-pf^2));//in volts prld1=(vlag1*po)/e2;// disp(prld,"percentage regulation on lagging load is,(%)=") disp(prld1,"percentage regulation on leading load is,(%)=") disp("part (c)") cl=85;//copper losses nloss=100;//no load losses fll=cl+nloss;//full load losses pf=0.8;//power factor flo=kva*pf;//efficiency effl=flo/(flo+fll);//efficiency hll=(1/2)^2*cl+nloss;//loss in watts op=(1/2)*kva*pf;//ouput power in watts efhl=op/(hll+op);//efficiency at half load disp(effl*100,"efficiency at full load is,(%)=") disp(efhl*100,"efficiency at half load is,(%)=")