clc clear //input kva=10;//kVA rating of the transformer vp=400;//voltage on primary side in volts vs=230;//voltage on secondary side in volts //short circuit test ppd1=18;//primary p.d. in volts ip1=25;//primary current in amperes inp1=120;//power input in watts //short circuit test ppd2=400;//primary p.d. in volts ip2=0.5;//primary current in amperes inp2=70;//power input in watts //calculations zp=ppd1/ip1;//equivalent primary impedance in ohms rp=inp1/(ip1^2);//equivalent resistance in ohms xp=((zp^2)-(rp^2))^0.5;//equivalent leakage reactance in ohms r0=(vp^2)/(1000*inp2);//resistance of parallel circuit phi=sin(acos(inp2/(vp*ip2)));//sine of power factor im=ip2*phi;//magnetizing current in amperes x0=vp/im;//reactance in ohms //output mprintf('the equivalent circuit parameters are \n Rp=%3.3f ohms \n Xp=%3.3f ohms \n r0=%3.3f kilo ohms \n x0=%3.1f ohms',rp,xp,r0,x0)