clc clear //input d=125;//power taken by an industrial load in kilowatts pf=0.6;//power factor v=415;//supply voltage in volts f=50;//supply frequency in hertz //calculations phii=acos(pf);//initial phase angle in radians kVAo=d/pf;//original kVA kvaro=d*tan(phii);//original kvar //for 0.9power factor phif=acos(0.9);//phase angle in radians kvarf=d*tan(phif);//final kvar kvarc=kvaro-kvarf;//capacitor kvar c1=(kvarc*(10^3)*(10^6))/(v*v*2*%pi*f);//capacitance in microfarad kVAf=d/0.9;//final kVA kVAr=kVAo-kVAf;//reduction in kVA //for unity power factor kvarC=kvaro;//capacitor kvar c2=(kvarC*(10^3)*(10^6))/(v*v*2*%pi*f);//capacitance in microfarad kVAF=d;//final kVA kVAR=kVAo-kVAF;//reduction in kVA //output mprintf('the required values of capacitance are %3.0f uF and %3.0f uF and the respective savings in kVA are %3.1f kVA and %3.1f kVA',c1,c2,kVAr,kVAR )