//voltage at sending end, percentage regulation,total line losses and transmission efficiency clear; clc; //soltion //given P=5000;//kW//power V=22000;//kV//recieving voltage pf=0.8;//peak factor R=4;//ohm//resistance X=6;//ohm//loop reactance Vr=V/sqrt(3); I=P*1000/(3*round(Vr)*pf); Vs=round(Vr)+(I*R*pf)+(I*X*sind(acosd(pf))); Vsl=sqrt(3)*Vs; printf("Sending end line voltage= %.3fkV\n",Vsl/1000) Pr=((Vsl-V)*100)/V; printf("Percentage regulation= %.2f percent\n",Pr); Ll=3*(round(I))^2*R/1000;//line losses printf("Total Line Losses= %.3fkW\n",Ll); nt=P*100/(P+Ll); printf("Transmission efficiency= %.3f percent",nt)