//Exa 9.6 clc; clear; close; //Given data : Vs=12;//kV n=4;//no. of uniits K=0.1;//shunt to mutual capacitance ratio V4=Vs;//kV V1=V4/(1+6*K+5*K^2+K^3);//kV V2=V1*(1+K);//kV V3=V1*(1+3*K+K^2);//kV V=V1+V2+V3+V4;//kV disp(V,"Maximum safe working voltage(kV)"); Strinf_eff=V/n/V4; disp(Strinf_eff*100,"Percentage String Efficiency(%)");