//Exa 7.7 clc; clear; close; format('v',5); //Given data : Pc1=53;//in kW V1=106;//in kV Pc2=98;//in kW V2=110.9;//in kV Vph1=V1/sqrt(3);//in kV Vph2=V2/sqrt(3);//in kV //Formula : Pc=3*244/del*(f+25)*sqrt(r/d)*(Vph-Vdo)^2*10^-5;//kW/Km disp("Using proportionality : Pc is proportional to (Vph-Vdo)^2"); disp("We have, Pc1/Pc2 = (Vph1-Vdo)^2/(Vph2-Vdo)^2"); Vdo=(Vph1-sqrt(Pc1/Pc2)*(Vph2))/(1-sqrt(Pc1/Pc2)); V3=113;//in kV Vph3=V3/sqrt(3);//in kV Pc3=Pc2*(Vph3-Vdo)^2/(Vph2-Vdo)^2;//in kW disp(Pc3,"Corona Loss at 113 kV in kW : "); VLine=sqrt(3)*Vdo;//in kV disp(VLine,"Disruptive critical voltage between lines(kV): ");