//Exa 11.4 clc; clear; close; //Given data : V1=11000;//Volt f=50;//Hz a=0.645;//cm^2 d=sqrt(4*a/%pi);//cm d=d/100;//m D=2.18/100;//m epsilon_r=3.5;//relative permitivity V=V1*sqrt(2)/sqrt(3);//V(assuming 3 phase system) gmax=2*V/d/log(D/d);//V/m gmax=gmax/10^5;//KV/cm disp(gmax,"Maximum electrostatic stress(kV/cm)"); gmin=2*V/D/log(D/d);//V/m gmin=gmin/10^5;//kV/cm disp(gmin,"Minimum electrostatic stress(kV/cm)"); C=0.024*epsilon_r/log10(D/d);//micro F disp(C*10^-6,"Capacitance per km length(F)");// Vp=V1/sqrt(3);//V Ic=2*%pi*f*C*10^-6*Vp;//A disp(Ic,"Charging Current per phase per km length(A)");