// Theory and Problems of Thermodynamics // Chapter 9 // Air_water Vapor Mixtures // Example 6 clear ;clc; //Given data V = 20*40*6 // dimensions of auditorium in cubic meters RH = 0.6 // relative humidy P = 101.325 // pressure of auditorium in kPa T = 303.15 // Temperature auditorium in K Ps_20 = 2.339 // saturation pressure of water at 20 degree C Ps_25 = 3.169 // saturation pressure of water at 25 degree C Ps_30 = 4.246 // saturation pressure of water at 30 degree C M = 18 // molecular weight of water R = 8.314 // gas constant // Calculations pw = RH*Ps_30 // partial pressure of water at 30 degree C SH = 0.622*pw/(P-pw) // specific humidity of air mw = pw*V*M/(R*T) // mass of water vapor in the auditorium ps = pw // at dew point from steam table T = 21.3 degree C // Output Results mprintf('(a) Partial pressure of water at 30 degree C = %4.4f kPa' , pw); mprintf('\n (b) Specific humidity of air = %4.3f kg H20/kg air' , SH); mprintf('\n (c) Mass of water vapor in the auditorium = %4.2f kg' , mw); mprintf('\n (d) Dew point = %4.4f kPa' , ps);