//To Find the Total Load and Total steady state voltage drop //Page 336 clc; clear; //Length in feet Lsd=100; //Service Drop Line Lsl=200; //Secondary Line SB=75; //Transformer Capacity in kVA pf=0.9; //Load Power Factor //From the Tables ISL=129.17; //Secondary Line Current ISD=41.67; //Service Drop Current KSD=0.01683; //Service Drop Cable Constant KSL=0.0136; //Secondary Cable Constant //for Transformer R=0.0101; //Resistance in per unit X=0.0143; //Reatance in per unit //From the Diagram ST=(3+2+8+6)+(5+6+7+4)+(6+7+8+10); //Total Load on transformer STpu=ST/SB; //In Per unit; //The Above value also corresponds to the Current as Well I=STpu; //Current in Per Unit VDT=I*((R*pf)+(X*sind(acosd(pf)))); //Voltage Drop in the Transformer VDSL=KSL*(Lsl*ISL/(10^4)); //Secondary Line VDSD=KSD*(Lsd*ISD/(10^4)); //Service Drop Line VD=VDT+VDSD+VDSL; //Total Voltage Drop printf('\na)The Load in transformer is %g kVA or %g pu\n',ST,STpu) printf('b) The Total Voltage Drop is %g pu V\n',VD)