//To find the percent voltage drop at the ends of the most remote laterals //Page 268 clc; clear; Vb=7200; //Base Voltage in V pf=0.9; //Power Factor Sm=10360; //Load on Main Feeder in kVA Vll=12.47; //Line to Line voltage in kV Imain=Sm/(sqrt(3)*Vll); //Current in Main Feeder //Note Suffix l means lateral and m means main Vph=7.2; //Phase Voltage in kV Sl=2*518; //Load on Lateral Feeder in kVA Ilateral=Sl/Vph; //Current in Laterals //Length of the Feeder //Length Constant Cm=5280; //Main Cl=1000; //Lateral Ll=5760/Cl; //Lateral Length Lm=3300/Cm; //Main Length //Constants for the particular cables from the tables rl=0.331; xLl=0.0300; rm=0.342; xam=0.458; xdm=0.1802; xLm=xam+xdm; //Voltage Drops for Normal Condition VDmainn=(Imain/2)*((rm*pf)+(xLm*sind(acosd(pf))))*Lm/2; VDlateraln=(Ilateral/2)*((rl*pf)+(xLl*sind(acosd(pf))))*Ll/2; perVDmainn=VDmainn*100/Vb; perVDlateraln=VDlateraln*100/Vb; TVDn=perVDmainn+perVDlateraln; //Voltage Drops for Worst Conditions VDmainw=(Imain)*((rm*pf)+(xLm*sind(acosd(pf))))*Lm/2; VDlateralw=(Ilateral)*((rl*pf)+(xLl*sind(acosd(pf))))*Ll; perVDmainw=VDmainw*100/Vb; perVDlateralw=VDlateralw*100/Vb; TVDw=perVDmainw+perVDlateralw; printf('\na)From Table A5, 300-kcmilACSR conductors, with 500A Ampacity is used for main\nand AWG #2 XLPE Al URD cable with 168A Ampacity\n') printf('b) The Total Voltage Drop in Percent for Normal Operation is %g percent\n',TVDn) printf('c) The Total Voltage Drop in Percent for Worst Condition is %g percent\n',TVDw) printf('d) The Voltage drop is met for Normal operation and NOT for emergency operation\n')