//To Determine the necessary realy and recloser coordination //Page 542 clc; clear; //For Recloser InstT=0.03; //From Curve A //Instaneous Time TimeD=0.17; //From Curve B //Time Delay //For Relay PickU=0.42; //From Curve C //Pick Up Reset=(1/10)*60; //Assuming a 60 s reset time for the relay with number 10 time dial setting RecloserOT=1; //Assumed Recloser Open Time RelayCTI=InstT/PickU; //Relay Closing Travel during instantaneous operation RelayRTI=(-1)*RecloserOT/Reset; //Relay Reset Travel during instantaneuos RelayCTD=TimeD/PickU; RelayRTD=(-1)*RecloserOT/Reset; //Relay Reset Travel during trip NetRelayTravel=RelayCTD-RelayRTD; printf('\nDuring Instantaneous Operation\n') printf('|Relay Closing Travel| < |Relay Rest Travel|\n') printf('|%g percent| < |%g percent|\n',RelayCTI*100,RelayRTI*100) printf('\nDuring the Delayed Tripping Operations\n') printf('Total Relay Travel is from:\n') printf('%g percent to %g percent to %g percent\n',RelayCTD*100,RelayRTD*100,RelayCTD*100) printf('Since this Net Total Relay Travel is less than 100 percent, \nthe desired recloser to relay coordination is accomplished\n')