// ELECTRIC POWER TRANSMISSION SYSTEM ENGINEERING ANALYSIS AND DESIGN // TURAN GONEN // CRC PRESS // SECOND EDITION // CHAPTER : 9 : SYMMETRICAL COMPONENTS AND FAULT ANALYSIS // EXAMPLE : 9.15 : clear ; clc ; close ; // Clear the work space and console // GIVEN DATA Y_11 = -2.2115*%i ; Y_12 = 0.2404*%i ; Y_21 = 0.2404*%i ; Y_22 = -2.0912*%i ; Y = [Y_11 Y_12 ; Y_21 Y_22] ; I_S1 = 2.3077*%i ; I_S2 = 1.9230*%i ; I_a1 = poly(0,'I_a1') ; I_a2 = poly(0,'I_a2') ; a = Y_12*I_S2 - Y_22*I_S1 ; b = (Y_12+Y_22)*I_a1 ; c = Y_12*I_S1 - Y_11*I_S2 ; d = (Y_12 + Y_11)*I_a1 ; V1 = (1/det(Y))*[(a-b) ; (c+d)] ; // Gives the uncoupled positive sequence N/W A = (Y_12+Y_22)*I_a2 ; B = (Y_12 + Y_11)*I_a2 ; V2 = (1/det(Y))*[A ; B] ; // Gives the uncoupled negative sequence N/W // DISPLAY RESULTS disp("EXAMPLE : 9.15 : SOLUTION :-") ; printf("\n (a) [V_a1 ; V_a11] = ") ; disp(V1) ; printf("\n Values of Uncoupled positive-sequence network \n") ; printf("\n (b) [V_a2 ; V_a22] = ") ; disp(V2) ; printf("\n Values of Uncoupled negative-sequence network \n") ;