// ELECTRIC POWER TRANSMISSION SYSTEM ENGINEERING ANALYSIS AND DESIGN // TURAN GONEN // CRC PRESS // SECOND EDITION // CHAPTER : 10 : PROTECTIVE EQUIPMENT AND TRANSMISSION SYSTEM PROTECTION // EXAMPLE : 10.7 : clear ; clc ; close ; // Clear the work space and console // GIVEN DATA Z_r1 = 0.0415692 + %i*0.4156922 ; // Required zone 1 setting . From result of exa 10.6 Z_r2 = 0.0623538 + %i*0.6235383 ; // Required zone 2 setting . From result of exa 10.6 Z_r3 = 0.1299038 + %i*1.2990381 ; // Required zone 3 setting . From result of exa 10.6 // CALCULATIONS // For case (a) theta1 = atand(imag(Z_r1),real(Z_r1)) ; Z_1 = abs(Z_r1)/cosd(theta1 - 30) ; // Zone 1 setting of mho relay R_12 // For case (b) theta2 = atand(imag(Z_r2),real(Z_r2)) ; Z_2 = abs(Z_r2)/cosd(theta2 - 30) ; // Zone 2 setting of mho relay R_12 // For case (b) theta3 = atand(imag(Z_r3),real(Z_r3)) ; Z_3 = abs(Z_r3)/cosd(theta3 - 30) ; // Zone 3 setting of mho relay R_12 // DISPLAY RESULTS disp("EXAMPLE : 10.7 : SOLUTION :-") ; printf("\n (a) Zone 1 setting of mho relay R_12 = %.4f Ω(secondary) \n",Z_1) ; printf("\n (b) Zone 2 setting of mho relay R_12 = %.4f Ω(secondary) \n",Z_2) ; printf("\n (c) Zone 3 setting of mho relay R_12 = %.4f Ω(secondary) \n",Z_3) ;