clc clear //INPUT DATA t1=15;//dry bulb temperature in Degree C t3=41;//heating coil temperature in Degree C t11=11;//wet bulb temperature in Degree C p=760;//pressure in mm of Hg x=0.4;//realtive humidity in percentage pva=9.83;//Saturation pressure in mm Hg ps2=33.68;//Saturation pressure in mm Hg cp=1.005;//specific pressure //CALCULATIONS t2=t3-(x*(t3-t1));//dry bulb temperature in Degree c pv1=(pva-((p-pva)*(t1-t11)*1.8)/(2800-(1.3*(1.8*t1+32))));//Saturation pressure in mm Hg w1=0.622*(pv1/(p-pv1));//Specific humidity in kg w.v./kg d.a x2=(pv1/ps2)*100;//realtive humidity in percentage h1=cp*t1+w1*(2500+1.88*t1);//Enthalpy of air per kg of dry air in kJ/kg d.a. h2=cp*t2+w1*(2500+1.88*t2);//Enthalpy of air per kg of dry air in kJ/kg d.a. Qa=h2-h1;//Sensible heat addition in kJ/kg d.a. //OUTPUT printf('(a)DBT is %3.1f Degree C \n (b)WBT is from the chart equal to 16.8 Degree C \n (c)RH is %3.2f percentage \n (d)Sensible heat addition is %3.2f kJ/kg d.a ',t2,x2,Qa)