//Exa 5.4 clc; clear; close; //Given Data : format('v',7); l=15*10^3;//in meter Pt=10000;//in KW cos_fir=0.8;//unitless VL=33*10^3;//in volt R=0.2*15;//in ohm/phase/15km X=0.4*15;//in ohm/phase/15km I=Pt*10^3/(sqrt(3)*VL*cos_fir);//in Ampere VR_phase=VL/sqrt(3);//in volt Vs=sqrt((VR_phase*cos_fir+I*R)^2+(VR_phase*sqrt(1-cos_fir^2)-I*X)^2); disp(Vs*sqrt(3)/1000,"Sending end voltage Vs(line) in KV :"); cos_fis=(VR_phase*cos_fir+I*R)/Vs;//unitless disp(cos_fis,"Sending end PF(leading) :"); disp(((Vs-VR_phase)/VR_phase)*100,"% Regulation : ");