//Exa 5.3 clc; clear; close; //Given Data : format('v',7); l=10*10^3;//in meter P_del=4000;//in KVA cos_fir=0.9;//unitless VL=11*10^3;//in volt R=0.2*10;//in ohm/phase/10km X=0.3*10;//in ohm/phase/10km I=P_del*10^3/(sqrt(3)*VL);//in Ampere VR_phase=VL/sqrt(3);//in volt Vs=sqrt((VR_phase*cos_fir+I*R)^2+(VR_phase*sqrt(1-cos_fir^2)+I*X)^2); disp(Vs*sqrt(3)/1000,"Sending end voltage Vs(line in KV) :"); disp(((Vs-VR_phase)/VR_phase)*100,"% Regulation : "); Losses3line=3*I^2*R;//in watt P_rec=P_del*cos_fir;//in KW Pin=P_rec+Losses3line/1000;//in KW ETA=P_rec/Pin;//unitless disp(ETA*100,"Transmission Efficiency(in %) :") cos_fis=(VR_phase*cos_fir+I*R)/Vs;//unitless disp(cos_fis,"Sending end PF(lag) :");